Product characteristics | Electrical designPNPOutput functionnormally openSensing range [mm]1.5HousingtubularDimensions [mm]Ø 6.5 / L = 50Electrical data | Operating voltage [V]10...36 DCCurrent consumption [mA]15; (24 V)Protection classIIIReverse polarity protectionyesOutputs | Electrical designPNPOutput functionnormally openMax. voltage drop switching output DC [V]2.5Permanent current rating of switching output DC [mA]200Switching frequency DC [Hz]1700Short-circuit protectionyesType of short-circuit protectionyes (non-latching)Overload protectionyesMonitoring range | Sensing range [mm]1.5Real sensing range Sr [mm]1.5 ± 10 %Operating distance [mm]0...1.22Accuracy / deviations | Correction factorstainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2Hysteresis [% of Sr]1...20Switch-point drift [% of Sr]-10...10Operating conditions | Ambient temperature [°C]0...60ProtectionIP 65; (with ifm socket duly screwed on: IP67)Tests / approvals | EMCEN 61000-4-2 ESD4 kV CD / 8 kV ADEN 61000-4-3 HF radiated10 V/mEN 61000-4-4 Burst2 kVEN 61000-4-5 Surge0,5 kV line to line, Ri: 2 OhmEN 61000-4-6 HF conducted10 VEN 55011class BVibration resistanceEN 60947-5-2 Shock resistanceEN 60947-5-2 MTTF [years]2359UL approvalTa-25...80 °CEnclosure typeType 1voltage supplyClass 2File number ULE174191